Molded case
circuit breakers (MCCB) from 100 through 400 amperes are assumed to have
standard thermal-magnetic trip units with instantaneous trips set at ten times
continuous ratings.
MCCB from
401 through 600 amperes are assumed to have electronic trip units.
Circuit
breakers above 600 amperes are assumed to be low-voltage power circuit breakers
with short-delay trip units set at 30 cycles.
When using
circuit breakers with short-delay trip units to achieve coordination, the
actual short-delay setting should be used if known. Formulas in Annex D of NFPA
70E or those in IEEE 1584 may be used to calculate incident energy when
settings are outside the limits of the calculator. In most cases, the incident
energy will exceed the capability of available PPE, i.e., over 100 cal/cm². If
making a detailed study of a system protected with circuit breakers, obtain the
actual opening times from the manufacturer.